Sale!

250 LPH RO Plant

185,000.00 135,000.00

250 LPH RO Plant

10 in stock

Description

BASIS OF DESIGN AND CAPACITY

Capacity utilization: 91-95% INPUTS (Wastewater Quality) To RO Plant:
Total Dissolved Solids: < 1000 PPM OUTPUT (Treated Water Quality)

TECHNICAL SPECIFICATIONS
1 RAW WATER PUMP
Purpose To feed the Dual Media Filter at pressure more than 2.0 bar, which is min. operating pressure for filter.
Specifications a) MOC : CI
b) Type : Horizontal Centrifugal
c) Power Required: 0.5 HP
d) Electrical : 230 V, Single phase , 50 hz
e) Make : Cri, Lubi or Equitant
i) Quantity : 1 No.

2 DUAL MEDIA FILTER
Purpose To remove the total suspended solids, dirt , iron and reduce silt density index which can foul the membranes
Specifications Vessel :
a) Make: Pentair or Equitant
b) Material of Construction: FRP
c) Diameter: 10”
d) Height : 54”
e) Testing Pressure : 10 kg/cm2
f) Opening : Top
g) Quantity : 1 No. Valve : ¾”
3 DOSING SYSTEM
Purpose To dose antiscalant chemical to protect the scaling formation on RO membranes.
Specifications a) MOC: PP
b) Capacity: 6 LPH
c) Pressure: 7 Bar
d) Qty.: 1 No.
e) Make: E-dose
4 MICRON FILTER
Purpose To remove the fine particles up to 05 microns and reduce silt density index levels to acceptable level.
Specifications Cartridge Filter & Housing
Housing:
a) MOC of Housing: PP
b) Length : 20”
c) Diameter: 6
d) Quantity : 1 No.
e) Cartridge : 20”
e) Make : Aqua Grand or Equitant
f) Cartridge MOC : Polypropylene
g) Length: 20”
h) Diameter : 4.5”
i) Quantity: 1 no.
k) Micron rating: 05 micron

5

HIGH PRESSURE PUMP
Purpose To feed the Reverse Osmosis Membrane at pressure more than the osmotic pressure taking into consideration flux rate, flow and recovery.
Specifications a) MOC : Stainless Steel
b) Type : Vertical Multistage
e) Power Required: 2 HP
f) Electrical: 230 V , Single phase, 50 hz
h) Make: CRI or Lubi

6 RO MEMBRANE
Purpose To remove the major part of TDS upto 98% by Reverse Osmosis Membranes arranged and designed to give adequate flow and recovery.
Specifications a) Type: Spiral Wounded
b) Diameter of Membrane: 4.0 inch
c) Length of Membranes: 1 Mt.
d) No. of Membranes : 1
f) Salt Rejection per Membrane: 98-99%
g) Make of Membranes: CSM 4040
h) System Recovery: 50-70 %
7 RO PRESSURE TUBE
Purpose To pack Reverse Osmosis Membranes and operate at high pressure up to 300 psi
Specifications a) MOC : FRP Composite
b) Diameter of Pressure Vessel : 4.2 inch
c) Length of Pressure Vessel : 2.3 m
d) No. Pressure Vessels: 1
e) No. of Membrane per Vessel: 1
f) Make: Roh
g) Position: Horizontal, Series
h) Arrays: 1 No.
8 ELECTRICAL PANAL
Purpose A control panel is provided as a safety measure for the pumps & other electrical items.
Specifications a) Complete Starters, Overload relays, and single-phase preventer for Pump.
b) Push Buttons
9 INSTRUMENTATION
Purpose a) Flow Meter : To measure the online flow of water
c) Low Pressure Switch : To protect RO pump from dry running
d) High Pressure Switch : To protect RO pump from back pressure
e) Pressure Gauges : For calculate ^P for each unit in RO system
Specifications Rota Meter :
Quantity : 2 Nos.( permeate & reject line)
Range : 1000 ltr per hour
Pressure Switch :
Quantity : 2 No.(Low & High)
Range : 0-450 psi
Make : Aster, India
Pressure Gauges :
Quantity : 4 No.
Range : 7 – 21 bar
Dial Size : 3 inches




Reviews

There are no reviews yet.

Be the first to review “250 LPH RO Plant”

Your email address will not be published. Required fields are marked *